SECTION 07570
SWD Urethane Company
CEMENTITIOUS COATED FOAM ROOF SYSTEM
Part 1 GENERAL
SUMMARY
Section Includes:
Cementitious Topped Coated foam roofing, as shown on drawings and specified
herein.
1.01 SYSTEM DESCRIPTION:
a. One inch (minimum) of sprayed polyurethane foam
(additional inches may be added and /or sloped depending upon desired
insulation value) on the deck surface with (25) mil thickness of white,
reflective 100% acrylic roof coating and 1/8Õ to ¼Õ of cementitious
coating with embedded aggregate for the final surface.
b. The low cost sustainable foam roof system is easily
maintained, repaired and upon inspection, may be re-coated with a ÒEver-GardÓ
cementitious protective coating after ten (10) years.
1.02 SUBMTTTALS
1.03 QUALITY ASSURANCE
1.04 DELIVERY, STORAGE AND HANDLING
1.05 PROJECT/SITE CONDITIONS
1.06 WARRANTY
Part 2. PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
a. Primer /Sealer is not usually needed on new wood deck
b. Primer/Sealer is almost always needed on metal deck
and metal roof
a. Fire hazard classification: This material meets UL
1256 requirements as a class A roof system when used with SWD Ever-Gard System
over combustible deck.
b. Polyurethane foam density and compressive strength
shall be uniform and consistent with specification. Minimal physical properties
shall not allow for multiple foam densities or compressive strengths to be
applied within multiple inches of specific foam.
c. SWD Polyurethane foam shall contain EPA-approved
245fa blowing agent and meet U.S. non-ozone depleting requirements of the U.S.
EPA mandate and international Montreal Protocol.
d. SWD Urethane Company, SWD 125 polyurethane foam with
HFC 245fa blowing agent is acceptable.
Physical Properties
Property ASTM
Procedure Values
Core Density, pcf
nominal * D-
1622 2.5
- 3.0
Compressive Strength,
psi D-2621
40.1
Tensile Strength, psi
D-1623
85.5
Open Cell Content, % D-2856
17.7
Closed Cell Content %
D-2856
82.3
Water Vapor
Transmission, ppi
E-96 1.0
R Value C-
177 6.8
k-Factor (initial) C-
177 0.148
4. SWD 125 ÒQuik-ShieldÓ polyurethane foam is acceptable.
a. Polyurethane Foam Density and Compressive Strength
shall be uniform and consistent with specification. Minimum Physical Properties
shall not allow for multiple foam densities or compressive strengths to be
spray-applied within multiple inches of specified foam.
b. Polyurethane Foam shall contain EPA-approved 245fa
blowing agent and meet U.S. non-ozone depleting requirements of the U.S. EPA
mandate and International Montreal Protocol. No polyurethane foam with
phased-out HCFC 141b blowing agent is acceptable.
c. SWD Urethane Company, SWD 125 Polyurethane Foam with
HFC 245fa ÒEnovateÓ blowing agent is acceptable
Physical
Properties
a. Property ASTM
Procedure Values
Fire Resistance E-84
Flame Spread E-84 15
Smoke Developed E-84 10
Solids Content
By Weight D-1353
70%
By Volume D-2697 60%
Solar Reflectance E-903 82%
Thermal Emittance E-408 91%
Tensile Strength: psi D-412
280
Elongation psi D-412
355
Water Vapor
Transmission, ppi E-96 1
Hardness –
Shore A Durometer
D-2240
60
Colors: Grey,
Buff, White
ASTM D-6083
– Standard Specificiation for Liquid-Applied Acrylic Coating
– Used in Roofing
(ALL FOLLOWING TESTS
PASSED)
Liquid requirements/
Film Properties:
Viscosity, Volume
Solids, Weight Solids, Initial Tensil Strength, Initial Elongation, Permeance,
Water Swelling, Wet Adhesion, Tear Resistance, Fungi Resistance
Note: SWD Urethane Company is an original "Energy Star"
partner and is CRRC approved.
1 Shall be manufactured
specifically for use with SWD 125 polyurethane foam and 1929F
ÔQuik-Shield ® acrylic elastomeric coating and SWD 1000 or SWD 2000 primer/
sealer.
2 Part A shall consist of
Cementitious dry-mix asbestos-free powder compound
3 Part B shall be 100%
acrylic, emulsion containing no styrene or Styrene Butadiene
4. The Cementitous coating shall be applied in two separate passes
resulting in 1/8Ó to ¼Ó
total (7-8 gallons per 100 square feet) thickness.
5. Aggregate topcoat shall include #6 crushed limestone at 64 lbs. per
100 square feet,
embedded in the wet coating.
6. Fire hazard classification: This system meets UL-790 requirements as
a Class A roof
covering when used with SWD Ever-Gard
Coated Foam Roof System.
PHYSICAL
PROPERTIES
Property
ASTM Procedure
Values
Solar Reflectance
E-903 81%
Thermal Emittance E-408 87%
UV Resistance D-822 2,000
hr/ No Effect
High Temperature
Stability D-794 No
Effect
Part 3. EXECUTION
3.01 EXAMINATION
3.02 PREPARATION
a. All loose gravel, dust and residue shall be removed
using power-vacuum equipment, power-sweeper, air-blowing or other suitable
means. (Special conditions may be required if asbestos products are a part of
roof removal.)
b. The existing roof shall be thoroughly inspected for
adhesion between felts, insulation and deck. Areas of poor adhesion, if any,
should be fastened. Blisters, buckles, wrinkles and fish-mouths shall be cut
out and/or fastened.
c. Remove or re-fasten all loose base flashing,
counter-flashing and gravel-stops, as required.
a. The metal roof deck shall be constructed of minimum
22-gauge steel. Construction shall conform to local building codes.
b. Ferrous Metal: Sandblast iron and steel surfaces,
which are not primed, shop-painted, or otherwise protected. Remove loose rust
and primer from shop-primed iron and steel surfaces by scraping or wire
brushing.
c. Non-Ferrous Metal : Clean galvanized metal, aluminum
and stainless steel surfaces, as recommended by the manufacturer issuing the
warranty.
d. If the metal surface is free of loose scale, rust,
weathered or chalking paint, it can be cleaned using compressed air-jet, vacuum
equipment, hand or powerbroom to remove loose dirt. Grease, oil or other
contaminants shall be removed with proper cleaning solutions.
e. Fluted metal decks require a suitable method of
covering or filling the flute prior to polyurethane foam application. Flutes
may be covered with a suitable board stock, or quality (4) inch tape prior to
spray-application of the polyurethane foam. Where a fire barrier is required,
apply Type X gypsum board, mechanically-fastened to the metal surface, to meet
local building code requirements.
f. Metal flutes 2 3/4 inches up to (3) in width, may be
taped with 4" adhesive tape then sprayed with a minimum of 1 1/2 inches of
foam.
a. Remove loose dirt, dust and debris by using
compressed air, vacuum equipment or broom. Oil and grease from release agents
or other contaminants shall be removed with proper cleaning solutions.
b. All joint openings in concrete decks that exceed 1/4
inch shall be grouted or caulked by others, prior to application of
polyurethane foam.
c. Priming is required on concrete surfaces and it is
recommended that due to hydration usually present in new concrete, poured
concrete decks be permitted to cure for twenty-eight (28) days prior to the
application of sprayed polyurethane foam. Cutting time off of (4) weeks is not
a short cut SWD recommends.
d. Sprayed polyurethane foam is not recommended for
application over lightweight or insulating concrete materials unless
underlayment and/or vent pans are installed. (Check with manufacturer prior to
installation of PUF roof system over lightweight concrete).
a. Deck must meet building code requirements for
resistance to wind uplift.
b. Plywood shall contain no more than 18% water, as
measured in accordance with ASTM Standards. Plywood shall be exterior grade not
less than 1/2" thick, nailed firmly in place.
c. Plywood joints in excess of 1/4 inch, shall be taped
or filled by others with a suitable sealant material, prior to application of
polyurethane foam.
d. Deck shall be free of loose dirt, grease, oil or
other contaminants prior to priming or foam application. Remove loose dirt or
debris by use of compressed air, vacuum or broom. No washing shall be
permitted.
e. Tongue & Groove Sheathing or Planking: Due to the
frequency of joints, possibility
of variable openings and effects of aging and shrinking, these surfaces must be
overlaid with a minimum of 1/4 inch thick, exterior grade plywood or other
suitable covering with a minimum (1) inch thickness.
a. Such materials used over fluted metal decks must be
installed with mechanical fasteners or adhesives.
b. Fasteners shall be installed to meet UL or Factory
Mutual wind uplift criteria or the appropriate local building code criteria.
Note: ICC uses a ÒFactor of 2Ó to qualify ÒWind Uplift Resistance.Ó A UL Uplift
Resistance of 160 pcf equals 80 MPH.
c. Boards shall be firmly butted together along edges
without gaps or openings. Joints exceeding 1/4 inch shall be caulked by others
with a suitable sealant material.
d. Care shall be taken to prevent mineral or gypsum
board from getting wet in storage on the job-site and after installation, prior
to being protected by foam. Moisture exposure may damage these materials and
require replacement.
e. Remove loose dirt and debris by using compressed air,
vacuum or broom. No power-broom is permitted due to possibility of damage.
f. Installed materials shall be protected from spills,
contaminants, oil, grease and solvents, etc.
3.03 INSTALLATION -
GENERAL
a. Using 1/2 inch CDX plywood and structural lumber
adhered mechanical1y to the substrate and vertical walls installed by others.
b. Using spray polyurethane foam (within certain sloping
requirements).
c. Using tapered insulation board which shall be secured
to the substrate with an adhesive recommended by the tapered board manufacturer
or with mechanical fasteners.
3.O4 INSTALLATION –
PRIMER/SEALER
3.05 INSTALLATION -
POLYURETHANE FOAM
3.06 INSTALLATION -
PROTECTIVE ELASTOMERIC COATING
1. Foam surface and adjacent surfaces to be coated,
shall be dry and completely free of degraded foam, foam over-spray, grease,
oil, dirt or other contaminants which interfere with proper coating adhesion,
dry and free of contaminants.
2. Do not apply coating materials when surface
temperature is less than 50 degrees F.
3. Any physical damage to the polyurethane foam shall be
repaired before coating.
4. Operator should wear soft-soled shoes to avoid
damaging the skin of the foam.
5. An additional application of base coat shall be
applied where foam surface has been sanded, planed or trimmed.
B.
Application
1. Acrylic Base Coat:
a. Shall be a contrasting color from the top coat to
insure adequate coverage.
b. Shall be applied on the same day, as the polyurethane
foam application, when possible.
c. The polyurethane foam shall be inspected for UV
oxidation if more than (72) hours has elapsed prior to application of base
coat.
d. Spray-apply elastomeric base coat over insulation at
the rate of (1) gallon per 100 square feet in one application.
2. Acrylic Top Coat:
a. Acrylic coating shall be a contrasting color from the base coat to
ensure adequate coverage.
b. Do not apply top coat until base coat has cured
properly. Normally, 12-24 hours is more than sufficient time for the base coat
to properly cure.
c. Spray-apply acrylic elastomeric top coat over the
base coat at the rate of (1 1/2) gallons per 100 square feet in one
application.
d. Coating passes shall be applied in cross-hatch pattern
at right angles to base coat passes to ensure more uniform coverage.
e. Coating shall extend up and over all polyurethane
foam on vent pipes, parapets and other penetrations and shall terminate a
minimum of (4) up to 12 inches above the foam. All top coat termination points
shall be straight-lined on parapet walls, vent pipes and other penetrations for
effective use and uniform appearance.
3. Cementitious Coating:
a. Cementitious coating with #6 limestone granules,
shall be applied as a wet final coating at the rate of 64 lbs. per 100 square
feet.
b. Cementitious coating including #6 limestone granules,
shall cover all acrylic coating
and terminate just
under acrylic top coating termination points, preserving straight-lines of
acrylic top coat on parapets, walls, vent pipes and other penetrations, as the
final straight-line appearance of the roof.
3.07 CLEANING